@openmep/hvac-domain

Deterministic round-duct sizing and supply/return/exhaust network propagation, as a library and a host-free CLI (openmep-hvac).

latest
npmnpm
Version
0.6.0
Version published
Weekly downloads
0
Maintainers
1
Weekly downloads
 
Created
Source

@openmep/hvac-domain

Deterministic, dependency-free ESM primitives for equal-friction round-duct sizing and supply, return, exhaust, and outside-air network propagation, plus a CLI that runs them on a JSON network with no editor or host. For agents, @openmep/mcp serves the same engine as MCP tools.

CLI

npx -p @openmep/hvac-domain openmep-hvac size network.json --pretty
npx -p @openmep/hvac-domain openmep-hvac duct --cfm 250 --role main --diameter-in 6
npx -p @openmep/hvac-domain openmep-hvac duct --cfm 900 --airflow return --width-in 14 --height-in 8

size takes a JSON array of NetworkItems (or { "items": [...] }): equipment, fittings, terminals with requiredCfm, and segments linked by connectedItemRefs. A segment may describe its existing section, {"shape":"round","diameterIn":6} or {"shape":"rect","widthIn":14,"heightIn":8}, and is then graded ok, undersized, or oversized by ASHRAE circular equivalent. Each terminal's airflowType (supply, return, exhaust, outside-air) picks the system; its CFM follows same-system or unknown items to equipment and is sized with that system's velocity caps. Output: summary, findings (missing-required-cfm: error for supply, warning for other systems; no-equipment-path, dangling-reference, mixed-system-segment, undersized, oversized), and segments with system, CFM, role, recommended standard diameter, velocity, and friction rate. Exit codes: 0, 1 with --fail-on-findings and error findings, 2 for invalid input (NetworkInputError with a JSON path) or an engine error. See examples/furnace-two-registers.items.json; the same document is what openmep-pascal items emits from a Pascal scene.

Library

import { recommendDuctSegments } from "@openmep/hvac-domain";

const result = recommendDuctSegments(items); // or { airflowTypes: ["supply"] }

sizeRoundDuct uses the ASHRAE friction-chart fit for galvanized round duct at standard air. sizeDuctForAirflow applies role-based velocity caps for supply, return, exhaust, or outside air; sizeSupplyRoundDuct is the supply convenience wrapper. recommendDuctSegments returns sorted arrays suitable for JSON serialization; recommendSupplyDuctSegments restricts it to supply. sizeSingleDuct and sizeNetworkInput are the CLI's two commands as functions.

Sizing from fan static pressure (Manual D friction rate)

Give the document a fan and the engine derives the friction rate the way ACCA Manual D does instead of using the fixed 0.08 in. w.g./100 ft:

{ "fan": { "externalStaticInWg": 0.70,
           "componentLossesInWg": { "dx-coil": 0.23, "filter": 0.18, "supply-outlet": 0.03, "return-grille": 0.03, "balancing-damper": 0.03 } },
  "items": [ /* segments with lengthFt, fittings/terminals with equivalentLengthFt */ ] }

Available static = external static − Σ device losses; total effective length = longest supply path + longest return path (measured lengthFt plus fitting equivalentLengthFt); FR = ASP × 100 / TEL. result.design reports each term and the governing paths; friction-rate-out-of-range warns when FR leaves Manual D's 0.06–0.18 window. examples/acca-manual-d-worksheet.network.json reproduces the published ACCA worksheet (ESP 0.70, losses 0.50, TEL 200 ft, FR 0.10). Equivalent lengths come from the designer or Manual D's fitting tables; the engine does not ship a fitting catalogue.

Scripting surface

For agents and scripts, one namespace covers the engine with stable names:

import { openmep } from "@openmep/hvac-domain/scripting";
const result = openmep.sizeNetwork(JSON.parse(text));   // validate + size + grade
const patched = openmep.applySizes(openmep.parseNetwork(doc), result);

See docs/scripting.md for the API table and three complete example scripts, and the openmep-engine skill in the repository's skills/ directory.

Engineering basis

The round-duct relation is Δp = 0.109136·Q^1.9/D^5.02, with pressure drop in in. w.g. per 100 ft, airflow in CFM, and diameter in inches. It assumes standard air (0.075 lb/ft³) and galvanized round duct roughness near 0.0003 ft. See the official ASHRAE Duct Design chapter for the standard-air friction chart and the 2025 ASHRAE Handbook—Fundamentals overview for the current volume. Velocity caps are transparent recommendations, not universal engineering limits.

Scope and limitations

  • Network propagation covers terminals with a positive requiredCfm in a classified system. An unknown item is shared by every system; if two systems load the same unclassified segment it is reported, not sized.
  • Recommendations are round. Existing rect and flat-oval sections are graded by ASHRAE circular equivalent; rectangular selection is not included.
  • connectedItemRefs are treated as an undirected graph because port direction is not represented.
  • Each terminal uses one lexically deterministic shortest compatible path to equipment. Loops are not hydraulically balanced and alternate paths do not share flow.
  • The calculation excludes fitting losses, pressure summation, fan selection, diversity, static-regain design, elevation, non-standard air, code compliance, and engineering judgment.

Use the output as a transparent preliminary sizing primitive; validate final designs with a qualified mechanical engineer.

Development

npm run build --workspace @openmep/hvac-domain
npm run test --workspace @openmep/hvac-domain

MIT licensed. See CONTRIBUTING.md and SECURITY.md.